Ordering Info and Specifications

Top  Previous  Next

Bus Probes are available in four versions:

BP#01 ambient temperature sensor.

BP#02 ambient temperature and humidity sensor.

BP#03 ambient light sensor.

BP#04 3-axis accelerometer.

Specifications

 

Interface

Half-duplex (two-wire) RS485 interface

Communications parameters:

38400-8-N-1

Protocol

Modbus RTU

Power supply range

4~15VDC

BP#01
(ambient temperature sensor)

- Measurement range: -40 to +125°C*;
- Measurement resolution: 0.25°C;
- Measurement accuracy: ±1°C.

BP#02
(ambient temperature and humidity sensor)

-Temperature measurement:
  -Measurement range: -25 to +50°C;
  -Measurement resolution: 0.5°C;
  -Measurement accuracy: not specified.
-Humidity measurement:
  -Measurement range: 10 to 90%RH;
  -Measurement resolution: 0.1%RH;
  -Measurement accuracy: ±5%RH.

BP#03
(ambient light sensor)

- Measurement range: 1 to 65528 lux;
- Measurement resolution: 1 lux;
- Measurement accuracy: 1 lux.

BP#04
(3-axis accelerometer)

- Independent X, Y, and Z axes;
- Measurement range for each axis: ±6G;
- Measurement resolution for each axis: 0.003G;
- Measurement accuracy for each axis: 0.1G.

Operating temperature range

-40 to +85 degrees C

Operating relative humidity

10-90%

Mechanical dimensions
(excluding terminal blocks)

40.0 x 36.0 x 19.0 mm

 

All specifications are subject to change without notice and are for reference only. Tibbo assumes no responsibility for any errors in this Manual, and does not make any commitment to update the information contained herein.

 